IEC 60793-2-10: Multimode Optical Fibre (A1-OM1 to A1-OM5)

IEC product specification for category A1 graded-index multimode fibre. Defines A1-OM1 to A1-OM5 and A1d, matching ISO/IEC OM grades.

IEC 60793-2-10 2019+A1:2022 3 min read

Sub-categories
A1-OM1 to A1-OM5
Plus A1d, 100/140 µm
OM4 and OM5 EMB
4 700 MHz·km
Minimum at 850 nm
Current edition
7.1 (2022)
Edition 7.0 (2019) + Amd 1
Full titleOptical fibres. Part 2-10: Product specifications. Sectional specification for category A1 multimode fibres
PublisherIEC, TC 86/SC 86A Fibres and cables
Current editionEdition 7.0, 22 May 2019, with Amendment 1, 27 January 2022 (consolidated edition 7.1)
StatusPublished. Edition 7.0 replaced the sixth edition of 2017
Also published asEN IEC 60793-2-10:2019 in Europe
Related standardsIEC 60793-2; IEC 60793-1 series (test methods); ISO/IEC 11801-1; ANSI/TIA-568.3; IEC 61280-4-1

What it covers

IEC 60793-2-10 is the IEC product specification for category A1 multimode fibre. A1 fibre is graded index. The standard covers the bare fibre, which is then built into cables and equipment.

Three types of requirement apply:

  • General requirements for all optical fibres, from IEC 60793-2.
  • Requirements common to all A1 fibres, in Clause 5.
  • Requirements for each sub-category, in the normative Annexes A to D.

Uses listed in the scope include data centres, LANs and SANs, and on-premises intra-building and inter-building installations.

Sub-categories and naming

The 2019 edition changed the names of the A1 sub-categories to match the OM grades in ISO/IEC standards. Table 1 of the standard cross-references the new and old names.

Current name2017 nameNominal coreISO/IEC 11801-1 cabled gradeAnnex
A1-OM1A1b62.5 µmOM1B
A1-OM2A1a.150 µmOM2A
A1-OM3A1a.250 µmOM3A
A1-OM4A1a.350 µmOM4A
A1-OM5A1a.450 µmOM5A
A1dA1d100 µmNoneC

The fibres are 50/125 µm, 62.5/125 µm and 100/140 µm graded index. A1-OM2 to A1-OM5 are four bandwidth grades of 50/125 µm fibre.

Each 50 µm grade comes in two macrobend levels. The suffix a means traditional macrobend loss. The suffix b means enhanced macrobend loss, that is, lower loss.

Bandwidth

Multimode grades are separated mainly by modal bandwidth. Overfilled launch bandwidth relates to LED-type sources. Effective modal bandwidth (EMB) relates to laser (VCSEL) sources and is assured by differential mode delay (DMD) requirements in Annex D.

GradeCoreOFL 850 nmOFL 1300 nmEMB 850 nm
OM350 µm1 500 MHz·km500 MHz·km2 000 MHz·km
OM450 µm3 500 MHz·km500 MHz·km4 700 MHz·km
OM550 µm3 500 MHz·km500 MHz·km4 700 MHz·km

These are the minimum values commonly published for A1-OM3 to A1-OM5 fibre and for the matching ISO/IEC 11801-1 cabled grades. The normative values are in Table A.3 of the standard. A1-OM5 is also specified for single or multi-wavelength systems from 850 nm to 950 nm, with a minimum EMB of 2 470 MHz·km at 953 nm. The standard includes informative wideband bandwidth data for A1-OM3 and A1-OM4 over the same range, but this is not normative.

How it relates to ISO/IEC 11801-1

IEC 60793-2-10 specifies fibre. ISO/IEC 11801-1 specifies cabled fibre grades, OM1 to OM5, for generic cabling. An OM4 cable normally contains A1-OM4 fibre.

  • The standard notes that OM1 and OM2 cables are not supported for new installations under ISO/IEC 11801-1:2017.
  • ISO/IEC 11801:2002 also allowed OM2 cable made with 62.5 µm fibre, and OM1 cable made with 50 µm fibre. Those combinations are not part of IEC 60793-2-10.
  • ANSI/TIA-568.3-D uses the same OM names as ISO/IEC 11801-1.

Test methods

Measurements use the IEC 60793-1 series. Examples include IEC 60793-1-20 for fibre geometry, 1-40 for attenuation, 1-41 for bandwidth, 1-47 for macrobending loss and 1-49 for differential mode delay. IEC 61280-4-1 is cited for multimode attenuation measurement of installed cable plant.

What to check on a datasheet

  • The IEC designation, such as A1-OM4, or the older A1a.3 on older documents. Both describe the same grade.
  • Whether the fibre is an a or b type, if tight bends are expected in enclosures.
  • EMB at 850 nm for laser-based applications, and EMB at 953 nm if the fibre is sold as OM5.
  • That cable and connectors in one link use the same core size. 50 µm and 62.5 µm fibres should not be mixed.