Installation & Earthing

BS EN 50174-1: Installation Specification and Quality Assurance

Part 1 of the EN 50174 series. Sets out the installation specification, quality plan, documentation, administration and maintenance of IT cabling.

BS EN 50174-1 2018+A1:2020 4 min read

Edition
2018+A1:2020
Supersedes EN 50174-1:2009 + A1:2011 + A2:2014
Duties split
2 clauses
Owner (4) and installer (5)
Revision
prEN 50174-1
Draft for comment, 2026
Full titleBS EN 50174-1:2018+A1:2020, Information technology. Cabling installation. Installation specification and quality assurance
PublisherCENELEC (CLC/TC 215). Published in the UK by BSI
Current editionBS EN 50174-1:2018+A1:2020, published 31 July 2020
StatusCurrent, under review. A revision (prEN 50174-1) is in progress
Related standardsBS EN 50174-2, BS EN 50174-3, BS EN 50173 series, BS EN 50310, EN 61935-1, ISO/IEC TR 14763-2-1, BS 6701

What it covers

BS EN 50174-1 is Part 1 of the three-part EN 50174 cabling installation series. It specifies requirements for three aspects of information technology cabling:

  • installation specification, quality assurance documentation and procedures;
  • documentation and administration;
  • operation and maintenance.

It applies to all types of IT cabling, including generic cabling designed to the EN 50173 series. Electrical safety, optical power, fire and EMC requirements are outside its scope. Part 2 covers installation planning and practice inside buildings, and Part 3 outside buildings.

EN 50174-1 is used during the specification phase and is intended to be referenced in contracts. It sets out the responsibilities of premises owners and installers separately.

Conformance

For a cabling installation to conform (clause 1.2):

  • the specification of the installation must meet Clause 4;
  • the installer must meet Clause 5;
  • the bonding system in the premises must be in accordance with EN 50310;
  • where a lightning protection system is required, it must be the integrated type to EN 62305-4 (other types are allowed only with agreed restrictions);
  • local regulations must be met.

Structure and key requirements

ClauseContent
4Requirements for specifying installations, primarily for the premises owner: installation specification, technical specification, scope of work, change control, planning (segregation from power, building entrance facilities, pathways, cabinets, spaces), products and labels, operating procedures and administration, maintenance
5Requirements for installers: quality plan, installation schedule, installation instructions, change control, documentation of the installed cabling, component acceptance, inspection and test equipment, labelling, surveys
6Installation and operational complexity (Tables 5 and 6)
Annex A (normative)Minimum requirements for technical specifications and quality plans
Annex B (normative)Polarity maintenance: connecting hardware for multiple optical fibres (duplex interfaces)
Annex F (normative)Sampling plans and marginal results (including non-compliant results) for balanced and optical fibre cabling
Annex G (informative)Reaction-to-fire performance of cables: Euroclass designations

Quality assurance

The owner, or a representative, writes an installation specification that includes a technical specification and quality assurance requirements. The installer provides a quality plan (5.1.2). Annex A lists the minimum content of both. Changes are managed under change control on both sides.

Documentation and administration

Clause 4.5.2 sets administration requirements, with minimum requirements for administration systems in Tables 3 and 4. Identifiers within administration systems are referenced to ISO/IEC TR 14763-2-1, and automated infrastructure management to EN 50667. Labels are covered for the owner in 4.3.4 and for the installer in 5.2.5. The installer must document the installed cabling (5.1.6).

Testing

EN 61935-1 is a normative reference for testing installed balanced cabling. Annex F sets sampling plans for balanced and optical fibre cabling to the EN 50173 series, lists the installed test parameters (Tables F.1 and F.2), and sets how marginal and non-compliant results are handled.

Remote powering

The 2018 edition revised the remote powering requirements to support power levels in IEEE 802.3bt. Table 2 defines remote powering installation categories and controls, and Figure 4 shows example labels indicating the category.

How it relates to other standards

DocumentRelationship
BS EN 50174-2 and -3Planning and installation practice inside and outside buildings
BS EN 50173 seriesGeneric cabling design; EN 50174-1 has specific requirements for cabling designed to it
BS EN 50310Bonding networks; required for conformance
ISO/IEC 14763-2International counterpart covering planning, installation and operation of customer premises cabling
BS 6701UK specification applied alongside the EN 50174 series

What it means in practice

  • Ask for, or provide, a written installation specification and a quality plan before work starts.
  • Agree the test regime and sampling plan at specification stage, including how marginal results will be treated.
  • Agree the identifier scheme and label format before installation, and hand over records that match the labels.
  • Where cabling will carry remote power, specify the remote powering category and label it.
  • Check cable reaction-to-fire class against the project requirement. Annex G explains Euroclass designations.

Related reading: How to read a cable test certificate · What is structured cabling?.

Share this article