ANSI/TIA-568.0: Generic Cabling for Customer Premises

North American base standard for generic telecommunications cabling. Sets structure, topology, distances, installation and testing for all premises.

ANSI/TIA-568.0 568.0-E (2020) + Addendum 1:2022 3 min read

Current revision
568.0-E
March 2020
Addendum 1
2022
Single twisted-pair cabling
Topology
Hierarchical star
Distributors C, B, A
Full titleGeneric Telecommunications Cabling for Customer Premises
PublisherTelecommunications Industry Association (TIA), ANSI-accredited
Current editionANSI/TIA-568.0-E, March 2020, with Addendum 1 (ANSI/TIA-568.0-E-1), July 2022
StatusCurrent. TIA work is under way on ANSI/TIA-568.1-F, which is planned to consolidate 568.0, 568.1 and TIA-862 (status October 2025).
Previous revisions568-C.0 (2009), 568.0-D (2015)
Related standardsANSI/TIA-568.1, 568.2, 568.3, 568.5, 569, 606, 607

What it covers

ANSI/TIA-568.0 specifies requirements for generic telecommunications cabling. It sets the requirements for cabling system structure, topologies and distances, installation, performance and testing.

It is written for any type of customer premises. The premises standards apply it to a specific building type. For example, ANSI/TIA-568.1 applies the generic structure to commercial buildings.

Detailed component and link transmission limits are set in the component standards: ANSI/TIA-568.2 for balanced twisted-pair, ANSI/TIA-568.3 for optical fibre and ANSI/TIA-568.5 for single twisted-pair.

Generic terms

Because it covers every premises type, 568.0 uses neutral names for connection points and cabling, rather than building terms such as telecommunications room or work area.

568.0 termMeaningTypical commercial building example
Distributor CInitial or central connection point in the hierarchical starMain cross-connect
Distributor BOptional intermediate connection point between Distributor A and Distributor COptional second cross-connect level
Distributor AIntermediate connection point between Distributor C and the equipment outletHorizontal cross-connect
Equipment outletFinal connection point in the hierarchical starTelecommunications outlet
Cabling subsystemRuns between
Cabling Subsystem 1Distributor A and the equipment outlet
Cabling Subsystem 2Distributor A and Distributor B
Cabling Subsystem 2 or 3Backbone cabling to Distributor C (from Distributor A or Distributor B)

A consolidation point is a connection facility within Cabling Subsystem 1. TIA committee TR-42.5 noted in October 2025 that the Cabling Subsystem 1 to 3 and Distributor A to C terms will be replaced in a future revision.

What 568.0 holds that 568.1 does not

568.1 is the commercial building application and refers back to 568.0 for its structure. Several general provisions sit only in 568.0:

  • the generic structure and hierarchical star topology that all premises standards build on
  • open office cabling, meaning consolidation points and multi-user telecommunications outlet assemblies, moved from 568.1 into 568.0 in the D revision
  • general installation requirements for cabling
  • general performance and testing requirements, with the detailed limits in the component standards
  • from Addendum 1 (2022), the topology, architecture and installation requirements for balanced single twisted-pair cabling

Revision history

DocumentDateNotes
568-C.0February 2009C revision
568-C.0 Addendum 1September 2010Updated balanced twisted-pair references
568-C.0 Addendum 2August 2012Updates to fibre polarity, application tables and fibre testing guidance
568.0-DSeptember 2015Revision
568.0-D Addendum 1July 2017Updated references and new media types
568.0-EMarch 2020Current revision
568.0-E-1July 2022Addendum 1: balanced single twisted-pair cabling

How it relates to other standards

  • ANSI/TIA-568.1 applies the 568.0 structure to commercial buildings.
  • ANSI/TIA-568.5 sets the single twisted-pair component and link requirements that 568.0-E-1 refers to.
  • ANSI/TIA-568.1-F, in development, is planned to combine 568.0, 568.1 and TIA-862 into one document.
  • ISO/IEC 11801-1 plays a similar generic role in the international series. It uses different terms and its own class system.

What it means in practice

  • Where a specification cites TIA-568, check which part and revision it means. Structure sits in 568.0 and 568.1; transmission and field test limits sit in 568.2, 568.3 and 568.5.
  • 568.0 and premises standards based on it use Distributor A, B and C. Map them to cross-connect names when coordinating with commercial building documents.
  • For consolidation points and multi-user outlets in open offices, look in 568.0, not 568.1.
  • For single-pair cabling to sensors, controllers and other building devices, use 568.0-E-1 for topology and installation together with 568.5.
  • Watch for ANSI/TIA-568.1-F, which TR-42.1 is developing to consolidate 568.0, 568.1 and TIA-862.