Approved Document B: Fire Safety Guidance for Cabling in England

Statutory fire safety guidance for England. What it says about protected circuits, cable supports, fire-stopping and cavity barriers.

Approved Document B 2019 ed. incl. 2026 amendments 5 min read

Protected circuits
PH 30
BS EN 50200 incl. Annex E
Cable supports
Class A1
Hold cables in place in fire
Latest change
30 Sep 2026
Second stairs at 18 m
Full titleApproved Document B: Fire safety. Volume 1: Dwellings. Volume 2: Buildings other than dwellings
PublisherHM Government (Ministry of Housing, Communities and Local Government)
Legal basisBuilding Regulations 2010, Schedule 1 Part B (requirements B1 to B5) and regulations 6(3), 7(2) and 38
Current edition2019 edition incorporating 2020, 2022, 2025 and 2026 amendments, collated with the 2029 amendments
StatusStatutory guidance. Following it is one way to show compliance with Part B
Applies toEngland. Wales and Scotland publish separate guidance

What it covers

Approved Document B (ADB) gives guidance on the fire safety requirements of the Building Regulations 2010 in England. Volume 1 covers dwellings, including dwellinghouses and flats. Volume 2 covers all other buildings.

RequirementSubject
B1Means of warning and escape
B2Internal fire spread (linings)
B3Internal fire spread (structure)
B4External fire spread
B5Access and facilities for the fire service

Most of ADB deals with building design. For cabling, the relevant guidance is on protected power circuits, fire-stopping of service penetrations, cavity barriers and the external wall rules.

Protected power circuits

A protected circuit is an electrical circuit that is protected against fire. ADB gives the same guidance in both volumes.

GuidanceVol 1 (flats)Vol 2
Cables sufficiently robust3.50a5.29a
Cable routes carefully selected and/or physically protected where cables may be exposed to damage3.50b5.29b
Methods of cable support class A1 rated, with at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire3.50c5.29c
Cables achieve PH 30 classification to BS EN 50200 (incorporating Annex E) or an equivalent standard3.51a5.30a
Circuit passes only through parts of the building where fire risk is negligible3.51b5.30b
Circuit separate from any circuit provided for another purpose3.51c5.30c
Guidance on cables for large and complex buildings is in BS 5839-1, BS 5266-1 and BS 85193.525.31

ADB does not refer to BS 7671. In BS 7671:2018+A4:2026, Regulation 521.10.202 deals with supporting wiring systems so they are not liable to premature collapse in a fire.

Fire-stopping of cable penetrations

Every joint, imperfect fit and opening for services through a fire-separating element should be sealed with fire-stopping so the fire resistance of the element is not impaired (Vol 1 para 9.1, Vol 2 para 10.1).

GuidanceVol 1Vol 2
Openings for pipes, ducts, conduits or cable through a fire resisting element: as few as possible, as small as practicable, and fire-stopped9.24b10.24b
Fire-stopping reinforced or supported by materials of class A2-s3, d2 or better where the unsupported span exceeds 100 mm, or where non-rigid materials are used (unless tested)9.2510.25
Proprietary, tested fire-stopping and sealing systems may be used. Not all suit every situation9.2610.26
Other materials: cement mortar; gypsum-based plaster; cement-based or gypsum-based vermiculite/perlite mixes; glass fibre, crushed rock, blast furnace slag or ceramic-based products; intumescent mastics9.2710.27
Further guidance: ASFP best practice guide and ASFP Red Book9.28 to 9.2910.28 to 10.29

Cavity barriers and cables

GuidanceVol 1 (dwellinghouses)Vol 2
Openings in cavity barriers limited to listed items, including the passage of cables or conduits containing one or more cables5.249.17
Cavity barriers fixed so they are not made ineffective by collapse of penetrating services in a fire, through failure of the supporting system or degradation of the service5.23b9.16b
Cavities over an undivided area exceeding 40 m in any direction have no size limit only if all listed conditions are met. Two of them are that supports and fixings in the cavity are class A1 (d) and that any electrical wiring is laid in metal trays or metal conduit (f)Not applicable9.12d and f

Volume 1 para 8.9 applies the dwellinghouse cavity barrier guidance (paras 5.21 to 5.24) to flats.

Cables and reaction to fire

  • ADB does not set reaction to fire classes for cables. It does not refer to BS EN 13501-6, the cable classification standard.
  • Wall and ceiling lining classes in ADB are to BS EN 13501-1.
  • For external walls of relevant buildings, regulation 7(2) requires materials of class A2-s1, d0 or A1. Regulation 7(3) exempts electrical installations and fibre optic cables, among other items.
  • The same exemption for electrical installations and fibre optic cables appears in the balcony guidance (Vol 1 para 10.10).

Cable reaction to fire classes for fixed installations are covered on the BS EN 13501-6 and EN 50575 pages.

Amendments and dates

AmendmentTakes effectMain changes
20252 March 2025Regulation 38 and fire safety information. Removal of national classes for reaction to fire and roofs. Sprinklers in new care homes
202630 September 2026More than one common stair in blocks of flats with a storey 18 m or more in height. Design provisions for evacuation lifts in blocks of flats
20292 September 2029Removal of national classes for fire resistance. Appendix B replaced

Each amendment has transitional provisions. The earlier text continues to apply where a building notice, initial notice or full plans application was made before the start date and the work is sufficiently progressed within the set period. For the 2026 amendments that period is 18 months (six months for the 2025 and 2029 amendments).

Wales and Scotland

  • Wales: the Welsh Government publishes its own Approved Document B in two volumes, with amendment slips, including one applicable from 20 December 2025.
  • Scotland: fire guidance is in Section 2 (Fire) of the Building Standards technical handbooks for domestic and non-domestic buildings. Revised handbooks apply to building warrant applications from 6 April 2026.

What it means in practice

  • For protected power circuits, ADB’s guidance is cable classified PH 30 to BS EN 50200 (incorporating Annex E) or an equivalent standard. For large and complex buildings it points to BS 5839-1, BS 5266-1 and BS 8519.
  • ADB’s guidance for protected circuits is class A1 rated cable supports that hold cables in place when exposed to fire.
  • Keep penetrations through fire resisting walls and floors few and small, and fire-stop them, using a proprietary tested system or another material suited to the situation (Vol 1 9.26 to 9.27, Vol 2 10.26 to 10.27).
  • Cables may pass through cavity barriers. Barriers should be fixed so that collapse of penetrating services in a fire is unlikely to make them ineffective.
  • In external walls of relevant buildings, electrical installations and fibre optic cables are exempt from the class A2-s1, d0 or A1 requirement under regulation 7(3).