Installation & Earthing

ISO/IEC 30129: Telecommunications Bonding Networks

International requirements for designing and installing telecommunications bonding networks in buildings, using protective, dedicated or mesh bonding.

ISO/IEC 30129 Ed. 1.2 2025 4 min read

Edition
1.2
2015 + Amd 1:2019 + Amd 2:2025
Network types
4
Star, ring, local mesh, mesh
Voltage limit
AC 1 000 V
Not for power above this
Full titleInformation technology. Telecommunications bonding networks for buildings and other structures
PublisherISO and IEC, joint technical committee ISO/IEC JTC 1/SC 25
Current editionEdition 1 (2015-10) with Amendment 1 (2019-02) and Amendment 2 (2025-07). Consolidated as Edition 1.2, 2025-07
StatusCurrent. ISO lists no newer edition under development
Related standardsBS EN 50310, ISO/IEC 14763-2, ANSI/TIA-607-E, IEC 60364-4-44, IEC 60364-5-54, ITU-T K.27

What it covers

ISO/IEC 30129 sets requirements and recommendations for the design and installation of bonds between electrically conductive elements in buildings and other structures. It applies during construction or refurbishment of buildings where telecommunications equipment is to be installed.

The aims are to:

  • Minimise d.c. and a.c. potential differences in telecommunications networks caused by electromagnetic disturbance, power transients and other causes, to reduce the risk of equipment malfunction. This also reduces the risk to equipment and its cabling from electrical hazards
  • Give the telecommunications installation a reliable signal reference, which improves immunity from electromagnetic interference (EMI)

It applies to the premises covered by ISO/IEC 14763-2, such as residential, office, industrial and data centre buildings. Telecommunications centres (operator buildings) are covered by ITU-T K.27 instead.

It does not apply to power supply distribution above AC 1 000 V. EMC requirements and safety requirements for power installations are outside its scope.

It is written for building architects, owners and managers, and for designers and installers of electrical and telecommunications cabling.

Structure

Clause or annexSubject
4Conformance
5Overview of bonding networks and equipment distribution
6Selecting the bonding network approach: assessment, network types, performance and d.c. resistance measurement
7Common features: protective bonding conductors, main earthing terminal (MET), entrance facility, conductors, connections, cabinets and racks, documentation
8Dedicated telecommunications bonding network
9Local bonding networks used with protective bonding networks (star and ring)
10Local bonding networks used with dedicated telecommunications bonding networks
11Mesh bonding networks, supplementary bonding grid, system reference potential plane and access floors
Annex AMaintenance of bonding network performance, including galvanic corrosion (normative)
Annex BBonding conductor cross-sectional area (normative)
Annex CAlternative terminology (informative)

Key technical content

Conformance route

An assessment to Clause 6 is required first. Based on the result:

  • Backbone and building entrance bonding either uses the protective bonding network, if it delivers the performance required, or meets Clause 8 for a dedicated network
  • Local bonding meets Clause 9 or Clause 10, or a mesh bonding network is used to Clause 11
  • Clause 7 applies to all telecommunications bonding networks
  • Conductor cross-sectional areas meet Clauses 7 to 11 as amended by the region-specific application of Annex B
  • Local regulations, including safety, are met

Clause 6 includes d.c. resistance requirements for protective bonding networks and for dedicated networks, and d.c. resistance measurements.

Components of a dedicated network

TermAbbreviationDefinition (summary)
Primary bonding busbarPBBConnected to the MET. Used to attach bonding backbone conductors and equipment bonding conductors
Secondary bonding busbarSBBBonding point for systems and equipment in the area served by a distributor
Telecommunications bonding conductorTBCConductor between the PBB and the MET
Telecommunications bonding backboneTBBConnects the PBB to its SBBs. Not intended as a fault current return path
Backbone bonding conductorBBCInterconnects telecommunications bonding backbones
Telecommunications equipment bonding conductorTEBCConnects a PBB or SBB to a supplementary bonding network, rack bonding conductor or item of equipment
Rack bonding busbarRBBAttachment point within a cabinet, frame or rack

Clause 8 also covers bonds to continuous conductive pathway systems and to structural metal. Bonding conductors are specified either for d.c. resistance control or for impedance control.

Mesh bonding

The standard describes four general types of bonding network: star, ring, local mesh and mesh. Clause 11 covers the mesh isolated bonding network (MESH-IBN), with a single point of connection, and the mesh bonding network (MESH-BN).

How it relates to other standards

StandardRelationship
BS EN 50310European counterpart. EN 50310:2016 transposed ISO/IEC 30129 with minimal editorial changes and adopted its title
ISO/IEC 14763-2Planning and installation of premises cabling. Leaves bonding networks to ISO/IEC 30129. ISO/IEC 30129 applies to the premises it addresses
ANSI/TIA-607North American bonding standard. Revision C (2015) changed its terms to harmonise with ISO/IEC 30129
IEC 60364 seriesElectrical installation rules for protective bonding and earthing, referenced normatively
ITU-T K.27Bonding in telecommunications centres, outside the scope of ISO/IEC 30129

What it means in practice

  • The standard does not mandate a dedicated network in every case. The Clause 6 assessment decides whether the existing protective bonding network is adequate.
  • A dedicated network connects to the electrical installation at the main earthing terminal through the TBC. In the UK, electrical safety earthing and bonding are covered by BS 7671.
  • Projects in Europe usually call up EN 50310 (BS EN 50310 in the UK). Projects specified to the ISO/IEC 11801 and 14763 series may call up ISO/IEC 30129. Check which one the contract names.
  • Annex A (normative) covers periodic activity to maintain bonding network performance, so record the bonding network in the installation documentation.