ANSI/TIA-598: Optical Fibre Cable Colour Coding

North American scheme for identifying fibres, tubes and units by colour, and recommended jacket colours for indoor fibre cables by fibre type.

ANSI/TIA-598 598-D 2 min read

Base colours
12
Blue to aqua
OM5 jacket
Lime
Addendum 2, 2018
Revision
598-D (2014)
Two addenda
Full titleOptical Fiber Cable Color Coding
PublisherTelecommunications Industry Association (TIA), engineering committee TR-42.12
Current editionANSI/TIA-598-D (July 2014), with Addendum 1 (additional colours for elements 13 to 16) and Addendum 2 (jacket colour for OM5 indoor cables, 2018)
Earlier revisions1995, 2001 and 2005 (598-C)
StatusCurrent
Related standardsANSI/TIA-568.3, TIA-492AAAE, IEC 60793-2-10, ISO/IEC 11801-1, EIA-359

What it covers

ANSI/TIA-598 defines the recommended identification scheme for individual fibres, fibre units and groups of units within a cable. It also covers colour coding of jackets for indoor premises cables.

Colours are defined by reference to the Munsell colour system (ASTM D1535) and EIA-359 standard colours.

The 12 fibre colours

Fibres are identified in groups of 12, in this fixed order:

PositionColourPositionColour
1Blue7Red
2Orange8Black
3Green9Yellow
4Brown10Violet
5Slate11Rose
6White12Aqua

The same sequence identifies buffer tubes and units. In a loose tube cable, tube 1 is blue and the first fibre in each tube is blue. Ribbons follow the same colour order for fibres 1 to 12.

Beyond 12

  • Positions 13 to 24 repeat the 12 colours with an added identifying mark, such as a stripe or tracer.
  • Addendum 1 defines four additional alternative colours for elements 13 to 16. It supports 16-fibre system architectures.

Jacket colours for indoor cables

TIA-598 gives recommended jacket colours that indicate the fibre type:

Fibre typeJacket colour
Multimode 62.5/125 µm (typically OM1)Orange
Multimode 50/125 µm (typically OM2)Orange
Laser-optimised multimode 50/125 µm (typically OM3 and OM4)Aqua
Wideband multimode 50/125 µm (OM5)Lime green
Single-modeYellow
Polarisation-maintaining single-modeBlue

Addendum 2 (2018) defines the recommended jacket colour for indoor cables containing wideband multimode fibre. This fibre is defined in TIA-492AAAE and in IEC 60793-2-10, and its cabled performance category is OM5 in ISO/IEC 11801-1.

Coloured jackets are generally an indoor convention. Indoor cables still need the fire performance required for their location.

StandardRelationship
ANSI/TIA-568.3Defines the performance of cabled fibre, including wideband multimode (OM5)
TIA-492AAAEWideband multimode fibre specification referenced by Addendum 2
IEC 60793-2-10Multimode fibre product specification referenced by Addendum 2
ISO/IEC 11801-1Designates the OM5 cabled fibre category
EIA-359Standard colours referenced for colour identification

What it means in practice

  • Count fibres from blue. Fibre 1 is blue, fibre 12 is aqua.
  • In loose tube cable, identify the tube colour first, then the fibre colour inside it.
  • Treat the jacket colour as a recommendation. Always confirm the fibre type from the jacket print legend before connecting or splicing.
  • Do not confuse aqua as a jacket colour (OM3 and OM4) with aqua as the twelfth fibre colour.
  • Lime distinguishes OM5 cable from the aqua used for OM3 and OM4.