Cabling Standards

ISO/IEC 11801-5: Generic Cabling for Data Centres

International standard for generic cabling in data centre computer rooms. Defines the ENI, MD, ZD, LDP and EO hierarchy and the classes used.

ISO/IEC 11801-5 2017+Cor 1:2018 4 min read

Edition
2017
Corrigendum 1:2018
Balanced classes
EA to FA, I, II
From ISO/IEC 11801-1
Replaces
ISO/IEC 24764
2010 + Amd 1:2014
Full titleInformation technology. Generic cabling for customer premises. Part 5: Data centres
PublisherISO and IEC, prepared by ISO/IEC JTC 1/SC 25
Current editionEdition 1, November 2017, with Corrigendum 1:2018
StatusPublished and current
ReplacesISO/IEC 24764:2010 and its Amendment 1:2014
European equivalentEN 50173-5:2018, published in the UK as BS EN 50173-5:2018

What it covers

ISO/IEC 11801-5 specifies generic cabling within and to the computer room spaces of data centre premises. It also applies to computer rooms inside other types of building.

A data centre site often includes offices and plant areas too. Those spaces are covered by other parts of the series:

  • office spaces: ISO/IEC 11801-2
  • industrial spaces: ISO/IEC 11801-3
  • distributed building services in data centre spaces: ISO/IEC 11801-6

It must be read with ISO/IEC 11801-1, which holds the class limits, component categories and test requirements.

Functional elements

The cabling is a hierarchy that runs from the point where external services enter to the outlets at the equipment cabinets.

ElementRole
External network interface (ENI)Point of connection to external (access provider) networks
Main distributor (MD)Central distributor for the computer room
Intermediate distributor (ID)Distributor between the MD and the zone distributors
Zone distributor (ZD)Distributor that serves a zone of equipment cabinets
Local distribution point (LDP)Optional connection point in the zone distribution cabling, between the ZD and the EO
Equipment outlet (EO)Fixed outlet at or in the equipment cabinet where zone distribution cabling ends

The cabling subsystems are named after the distributors they connect:

  • network access cabling: from an MD, ID or ZD to the ENI
  • main distribution cabling: MD to IDs or ZDs
  • intermediate distribution cabling: ID to ZDs
  • zone distribution cabling: ZD to EO, optionally via an LDP

Classes and media

MediaRecognised in EN 50173-5:2018
Balanced channel and link classesEA, F, FA, I and II
Balanced cable categories5, 6, 6A, 7, 7A, 8.1 and 8.2
Cabled optical fibre categoriesOM3, OM4, OM5, OS1a and OS2

The ISO text uses the same class range, EA to FA plus I and II. It gives zone distribution length assumptions separately for Classes EA to FA and for Classes I and II, with channel length equations for each. Classes I and II are limited to short channels of up to 30 m with no more than two connections, as set by ISO/IEC 11801-1.

Other tables give length assumptions and equations for cabling between distributors and for network access cabling, and list the connecting hardware to be used at the EO.

Changes from ISO/IEC 24764

  • Restructured to hold only requirements specific to data centres, with common requirements moved to ISO/IEC 11801-1
  • Balanced cabling channels Class I and Class II added
  • Examples of structures added in Annex C
  • Examples of networking architectures added in Annex D

How it relates to other standards

  • EN 50173-5:2018 is the European equivalent and uses the same structure. It supersedes EN 50173-5:2007 and its amendments. BSI publishes it as BS EN 50173-5:2018, which supersedes BS EN 50173-5:2007+A2:2012.
  • ANSI/TIA-942 is the North American data centre standard. It defines its own data centre spaces, while ISO/IEC 11801-5 defines functional elements. TIA-942 also covers site, electrical, mechanical and resilience topics that ISO/IEC 11801-5 does not.
  • ISO/IEC 11801-1 sets the performance of each class and category.
  • BS EN 50174-1 and -2 cover installation planning and practice, including data centre spaces.

What it means in practice

  • Name the distributors on drawings using the standard terms (ENI, MD, ZD, LDP, EO) so designs can be checked against the length tables.
  • Use the channel length equations in the standard, not the 90 m / 100 m office rule, when a zone channel includes an LDP or extra connections.
  • Confirm the class required at each subsystem. Class I or II is only for short channels, such as within a row.
  • Specify cabled fibre by category (for example OM4 or OS2) and state the connector at the EO.
  • Check that test reports use ISO class limits where ISO/IEC 11801-5 or EN 50173-5 is the contract standard.

Related reading: OM4 vs OM5 fibre: what’s the difference? · Single-mode vs multimode fibre explained.