ANSI/TIA-942: Data Centre Telecommunications Infrastructure

North American standard for data centre infrastructure. Defines the ER, MDA, IDA, HDA, ZDA and EDA spaces and Rated-1 to Rated-4 levels.

ANSI/TIA-942 942-C (2024) 3 min read

Current revision
942-C
Published May 2024
Rated levels
Rated-1 to Rated-4
Basic to fault tolerant
Cabinet width
800 mm minimum
In MDA, IDA and HDA
Full titleANSI/TIA-942, Telecommunications Infrastructure Standard for Data Centers
PublisherTelecommunications Industry Association (TIA), committee TR-42.1
Current revisionANSI/TIA-942-C, approved February 2024 and published May 2024
StatusCurrent. An addendum related to AI data centres is listed as new work (TR-42, October 2025)
Previous revisionsTIA-942 (2005), 942-A (2012), 942-B with Addendum 942-B-1 on edge data centres
Related standardsISO/IEC 11801-5, EN 50173-5, ANSI/TIA-568 series, ANSI/TIA-606

What it covers

ANSI/TIA-942 specifies minimum requirements for data centre infrastructure. The core is telecommunications cabling, spaces and topology. It also covers site location, architecture, electrical, mechanical, fire safety, physical security and monitoring, and gives a system of resilience ratings.

ISO/IEC 11801-5 and EN 50173-5 deal with the cabling only.

Data centre spaces

The cabling follows a hierarchical star topology based on the TIA commercial building model.

SpaceFull nameRole
EREntrance roomAccess provider equipment and demarcation points; interface with campus cabling. Recommended to be outside the computer room for security
MDAMain distribution areaMain cross-connect and core routers and switches. At least one is required
IDAIntermediate distribution areaIntermediate cross-connect for large data centres, between the MDA and HDAs
HDAHorizontal distribution areaHorizontal cross-connect and the equipment that serves the equipment distribution areas
ZDAZone distribution areaOptional interconnection point in horizontal cabling between the HDA and EDA. No cross-connects or active equipment
EDAEquipment distribution areaEquipment cabinets and racks where horizontal cabling terminates

In small data centres some of these functions can be combined, for example the MDA and HDA in one space.

Rated levels

LevelDescription
Rated-1Basic site infrastructure
Rated-2Redundant component site infrastructure
Rated-3Concurrently maintainable site infrastructure
Rated-4Fault tolerant site infrastructure

In 942-C the annex on infrastructure rating is normative, but any rating system may be used. The rating tables in Annex D are normative where the TIA-942 rating system is used. TIA ratings are separate from the Uptime Institute Tier scheme.

What changed in 942-C

  • Incorporates Addendum 942-B-1 on edge data centres, with an annex on micro edge data centre types
  • Recognises single balanced twisted-pair cable for horizontal cabling
  • Allows any optical fibre connector that meets ANSI/TIA-568.3, except at the equipment outlet, where LC and MPO connectors are still required
  • Where balanced twisted-pair cabling is used for wireless access points, requires at least two Category 6A or higher cabling runs to each one
  • Requires cabinets in the MDA, IDA and HDA to be at least 800 mm wide
  • Sets a minimum floor loading of 5 kPa for computer rooms under 20 m²
  • Recommends at least two optical fibres for horizontal and backbone cabling
  • Updates temperature and humidity references to the ASHRAE TC 9.9 recommended envelope, and adds an informative annex on immersion cooling
  • Makes several annexes normative, including space considerations, site selection and building design

Earlier changes still relevant

942-A (2012) added the intermediate distribution area, removed the 100 m length limit for optical fibre horizontal cabling (length is set by the application), and aligned connectors with international standards: LC for one or two fibres and MPO for more than two.

How it relates to other standards

TIA-942 defines data centre spaces, while ISO/IEC 11801-5 and EN 50173-5 define functional elements. Component and test performance in TIA-942 comes from ANSI/TIA-568.2 (twisted-pair) and ANSI/TIA-568.3 (optical fibre). Labelling follows ANSI/TIA-606.

What it means in practice

  • On UK and European projects, check which document is the contract standard.
  • If a client asks for a Rated level, confirm whether they mean TIA-942 ratings or another scheme.
  • Plan cabinet widths of 800 mm or more in distribution areas to leave room for cable management.
  • Provide LC or MPO connectivity at the equipment outlet in the EDA.
  • Where balanced twisted-pair cabling is used for wireless access points, allow at least two Category 6A cabling runs to each one.

Related reading: Fibre optic connectors explained: LC vs SC · OM4 vs OM5 fibre: what’s the difference?.