Cabling Standards

KNX and EN 50090: Home and Building Electronic Systems (HBES)

KNX is published as EN 50090 and as parts of ISO/IEC 14543-3. EN 50090-5-2 sets the TP1 bus: SELV, 9600 bit/s, up to 1000 m per segment.

EN 50090 / ISO/IEC 14543-3 (KNX) TP1: EN 50090-5-2:2020 5 min read

Cable per segment
1000 m
Maximum, TP1 physical segment
Device to device
700 m
Maximum distance
Devices per segment
64 or 256
TP1-64 or TP1-256
Full titleEN 50090 series, Home and Building Electronic Systems (HBES). TP1 bus: EN 50090-5-2, Part 5-2: Media and media dependent layers, Network based on HBES Class 1, Twisted Pair
PublisherCENELEC, committee CLC/TC 205, with KNX Association as co-operation partner. International series: ISO/IEC 14543-3 (ISO/IEC JTC 1/SC 25)
Specification ownerKNX Association, founder and owner of the KNX Standard, which maintains the KNX specifications and runs product certification
Current edition (TP1)EN 50090-5-2:2020, published April 2020, replacing EN 50090-5-2:2004. National withdrawal date for conflicting standards: 10 April 2023
StatusEN 50090-5-2:2020 published and current. EN 50090-9-1:2004 (installation requirements) withdrawn by CENELEC with effect from 1 February 2017. BSI still lists BS EN 50090-9-1:2004 as current
Related standardsBS 7671, BS EN 50174-2, EN 50288 and EN 50290 cable series, ISO/IEC 11801-6

What it covers

KNX is an open protocol for home and building control: lighting, blinds, heating, ventilation, metering and similar functions. Its protocol and media are published as the European EN 50090 series and as parts of the international ISO/IEC 14543-3 series. The KNX specifications were also published by CEN as EN 13321-1 and EN 13321-2.

The KNX Association, founder and owner of the KNX Standard, maintains the KNX specifications and runs the certification scheme for KNX products. EN 50090-5-2:2020 states that it was prepared with the help of the KNX Association as a CENELEC co-operation partner.

This page covers twisted pair, known as TP1, which carries data and power on one pair of wires.

Structure of EN 50090

PartSubject
Part 1Standardisation structure
Part 3Aspects of application
Part 4Media independent layers (for example EN 50090-4-2: transport, network and general parts of the data link layer for HBES Class 1)
Part 5Media and media dependent layers (EN 50090-5-2: TP1)
Part 6Interfaces
Part 7System management

The EN 50090-5-2:2020 foreword lists these parts and notes that Part 2 has been withdrawn.

Installation part (withdrawn)

EN 50090-9-1:2004, Installation requirements: Generic cabling for HBES Class 1 Twisted Pair, gave rules for planning, engineering, installing and commissioning Class 1 twisted-pair cabling. It covered cable supports, cables, connectors and coexistence with mains power and other networks. CENELEC withdrew it with effect from 1 February 2017. No replacement is listed. BSI still lists BS EN 50090-9-1:2004 as current.

International series

ISO/IEC 14543-3 is the international counterpart, prepared by ISO/IEC JTC 1/SC 25. Its first parts were published in 2006. For example, ISO/IEC 14543-3-1:2006 (edition 1.0) specifies the application layer for network based control of HES Class 1.

TP1 system parameters

Table 1 of EN 50090-5-2:2020 gives the main system parameters. They apply only to cable that meets the bus cable requirements in the standard (subclause 4.4) and to devices drawing no more than 12 mA from the bus.

CharacteristicTP1-64TP1-256
MediumShielded twisted pair (shield not mandatory)Same
TopologyLinear, star, tree or mixedSame
Baud rate9600 bps9600 bps
Power supply unit30 V DCSame
Power supplies per physical segmentMaximum 2Maximum 2
Devices per physical segmentMaximum 64Maximum 256
Total cable length per physical segmentMaximum 1000 mMaximum 1000 m
Distance between two devicesMaximum 700 mMaximum 700 m
Device bus consumption3 mA to 12 mASame
Protection against shockSELVSELV

A TP1-64 segment can be extended with up to three more physical segments through bridges, giving a line of up to 256 devices. TP1-256 is backwards compatible with TP1-64. Line couplers join lines into a zone, and backbone couplers join up to 16 zones.

A logical 1 is the idle state of the bus. The standard gives a bit time of 104 µs and a DC level of 21 V to 32 V for a logical 1.

Bus cable requirements

EN 50090-5-2:2020 sets bus cable requirements in subclause 4.4. Its normative references include the EN 50290 communication cable series, IEC 60189-2, IEC 60332-1 and IEC 60754-2. The KNX Association certification scheme uses a Manufacturer’s Declaration on KNX Cables, which lists these values:

PropertyValue in KNX cable declaration
Conductor diameter0.8 mm to 1.0 mm, copper, solid or stranded
Pairs and coloursTwo pairs: red/black and white/yellow
Maximum cable length1000 m (standardised cable)
Loop resistance20 to 75 ohm/km (standardised cable)
Capacitance, wire to wire10 to 100 nF/km at 10 kHz
TwistMinimum 5 twists per metre
High voltage test2 kV AC, 50 Hz, or 4 kV AC where a country requires it
Core to core withstand800 V AC
Environmental and mechanicalRelevant parts of EN 50288 or EN 50290

The declaration also lists a screen over the whole cable diameter with a drain wire of at least 0.4 mm, and requires an outer sheath. A cable that is not standardised may have a shorter maximum length, which must be stated in its documentation. EN 50090-5-2 Table 1 does not make a shield mandatory.

SELV and separation from mains

TP1 operates under SELV conditions. In UK installations, BS 7671 sets requirements for segregating circuits of different voltage bands. BS EN 50174-2 gives separation rules for information technology cabling from power cabling. See the library pages for those standards. CENELEC has withdrawn the EN 50090 installation part (EN 50090-9-1).

What it means in practice

  • Use bus cable that meets subclause 4.4 of EN 50090-5-2. The 1000 m and 700 m limits apply only to such cable.
  • Keep each physical segment to 1000 m of cable in total and no more than 700 m between any two devices.
  • Check whether devices are TP1-64 or TP1-256 before planning more than 64 devices on one segment. Use no more than two power supply units per segment.
  • Segregate the bus from mains circuits as required by BS 7671. For separation from power cabling, see also the BS EN 50174-2 rules for information technology cabling.
  • EN 50090-9-1 was withdrawn by CENELEC in 2017, but BSI still lists BS EN 50090-9-1:2004 as current. Confirm with the specifier before citing it.