Cabling Standards

ANSI/TIA-1179: Healthcare Facility Cabling

The TIA standard for telecommunications cabling, pathways and spaces in hospitals, clinics and other healthcare facilities.

ANSI/TIA-1179 1179-B (2023) 3 min read

Current revision
1179-B
June 2023
Work area groups
11
Defined in the 2010 edition
Wireless APs
2 x Cat 6A
Minimum per access point
Full titleANSI/TIA-1179-B, Healthcare Facility Telecommunications Infrastructure Standard
PublisherTelecommunications Industry Association (TIA), subcommittee TR-42.1
Current revisionANSI/TIA-1179-B, approved 27 June 2023
StatusCurrent. Supersedes ANSI/TIA-1179-A (July 2017)
Previous revisionsTIA-1179-A (2017); TIA-1179, first published 2010
Related standardsANSI/TIA-568.0, 568.1, 568.2, 568.3, 569, 606, 607

What it covers

ANSI/TIA-1179 sets requirements for telecommunications infrastructure in healthcare facilities such as hospitals and clinics. It covers cabling, cabling topologies and cabling distances. It also covers pathways and spaces, including their size and location, and ancillary requirements.

The cabling is intended to support clinical and non-clinical systems. The standard gives nurse call, security and access control as examples of systems that use, or can use, IP-based infrastructure.

The standard was started by healthcare facility end users who approached TIA. It recognises that some spaces have restrictions on access after occupancy, for example for infection control.

Structure of 1179-B

Revision B was restructured to follow the general format of ANSI/TIA-568.1. Its main clauses are:

ClausesSubject
4 and 5Cabling system structure and topology
6 to 8Entrance facilities, equipment rooms, telecommunications rooms and enclosures
9 and 10Backbone cabling (cabling subsystems 2 and 3) and horizontal cabling (cabling subsystem 1)
11 and 12Work areas and coverage areas
13Multi-tenant building spaces
14 to 16Cabling installation, administration and office area requirements, and cabling performance
17 to 20Data centres, intelligent building systems, educational facilities and outside plant campus cabling
21 and 22Cabling for wireless access points and distributed antenna systems
23 to 27Grounding and bonding, pathways, firestopping, security and administration

Healthcare work areas

TIA-1179 (2010) defined 11 work area classifications:

  • Patient services
  • Surgery, procedure and operating rooms
  • Emergency
  • Ambulatory care
  • Women’s health
  • Diagnostic and treatment
  • Caregiver
  • Service and support
  • Facilities
  • Operations
  • Critical care

Clause 11.3.2 of 1179-B covers outlet density, and Table 3 gives recommended work area outlet densities. The 2010 edition graded areas as low, medium or high density.

Recognised media and minimum categories

Item1179 (2010)1179-A (2017)1179-B (2023)
Horizontal balanced twisted-pairCategory 6 recommended minimumCategory 6A minimumNo change listed
Backbone balanced twisted-pairNot covered hereCategory 6A minimumNo change listed
Multimode fibre50 µm for high-bandwidth usesOM4 recommended minimumNo change listed
Broadband coaxial cablingNot covered hereRequirements addedNo change listed
Single twisted-pair cablingNoNoAdded as recognised media
Wireless access pointsNot covered hereRecommendations addedAt least two Category 6A or higher runs per access point

1179-A also required at least two fibres in optical fibre backbone cabling, allowed array connectors for fibre in the work area, and allowed multi-user telecommunications outlet assemblies (MUTOAs) and consolidation points.

The changes listed for 1179-B are updated references, single twisted-pair cabling as recognised media, the wireless access point minimum and the new structure. Check other minimums against the 1179-B text.

Pathways and spaces

  • 1179-A added requirements for pathways and spaces that supplement ANSI/TIA-569, plus bonding and grounding, firestopping and multi-tenant building spaces.
  • Enclosed pathways are advised where infection control applies, particularly in air-handling spaces.
  • Segregation of networks and colour-coding of cables are recommended. No specific colours are assigned.

How it relates to other standards

  • ANSI/TIA-568.0 and 568.1 are normative references. 1179 applies the 568 series structure and adds healthcare requirements.
  • ANSI/TIA-568.2 and 568.3 set the component and cabling performance for twisted-pair and optical fibre.
  • ANSI/TIA-569, 606 and 607 cover pathways and spaces, administration, and bonding and grounding.
  • ISO/IEC 11801 and EN 50173 have no healthcare-specific part.

What it means in practice

  • Check which revision the specification calls for. 1179-B replaced 1179-A in 2023.
  • Use the work area tables to plan outlet counts per room type rather than a single figure for the whole building.
  • Allow for at least two Category 6A or higher runs to each wireless access point.
  • Plan pathways for infection control. Access to some spaces may be restricted once the building is occupied.
  • Where the project is in the UK, confirm how 1179 sits alongside the ISO/IEC 11801 or EN 50173 series in the contract documents.

Related reading: The complete guide to Cat6A cable · What is structured cabling?.