BS EN 50200: Fire Resistance of Small Emergency Cables

Flame and shock test for unprotected cables up to 20 mm used in emergency circuits. Gives PH15 to PH120 classes under EN 13501-3.

BS EN 50200 2015 4 min read

Flame
842 °C
Notional constant temperature
Cable size
≤ 20 mm
Overall diameter
Classes
PH15 to PH120
Via EN 13501-3
Full titleMethod of test for resistance to fire of unprotected small cables for use in emergency circuits
PublisherCENELEC (CLC/TC 20, Electric cables); published in the UK by BSI
Current editionBS EN 50200:2015, published 31 December 2015, identical to EN 50200:2015
StatusCurrent. Confirmed after CENELEC systematic review (review enquiry from 1 October 2025; stage: decision to confirm)
SupersedesEN 50200:2006
Related standardsEN 13501-3, BS 8434-2, BS 8491, IEC 60331 series

What it covers

EN 50200 specifies a test method for cables designed to have intrinsic resistance to fire, for use as emergency circuits for alarm, lighting and communication purposes.

It applies to cables of rated voltage up to 600 V/1 000 V, including cables rated below 80 V and optical fibre cables. The method is limited to cables with an overall diameter not exceeding 20 mm.

Detailed procedures are given for electric power and control cables. Details for copper data and telecom cables and for optical cables are given in the relevant standards of CLC/TC 46X and CLC/TC 86A, which refer back to EN 50200 for the basic test method.

When the test is used in support of EN 13501-3, it only applies to cables of less than 20 mm diameter and, for metallic conductor cables, to conductor sizes up to and including 2.5 mm².

The test set-up

ItemRequirement
SampleAt least 1 200 mm of cable, bent into an approximate U shape at the manufacturer’s declared minimum bending radius
MountingFixed with earthed copper P clips to a non-combustible board (900 ± 100) mm long, (300 ± 50) mm high, (10 ± 2) mm thick; wall mass (10 ± 0.5) kg on rubber bushes
BurnerHorizontal ribbon propane burner, nominal face 500 mm long and 10 mm wide, (40 ± 2) mm from the wall
FuelPropane (160 ± 6) mg/s, controlled by mass flow meters or controllers
VerificationMean thermocouple reading over 10 min within 830 °C +40/0 °C; the two thermocouples within 40 °C of each other
ShockMild steel bar 25 mm diameter, 600 mm long, pivoted and dropped from 60° to strike the top support of the wall
CircuitConductors energised through 2 A fuses (IEC 60269-3, type DII) or an equivalent circuit breaker; load and indicator (for example a lamp) on each conductor or group of conductors
EnvironmentDraught-free chamber of at least 20 m³, at (25 ± 15) °C at the start

The scope describes the flame as a constant temperature attack of a notional 842 °C. The European foreword describes it as a minimum test temperature of 830 °C, with the cable tested in a representative installed condition at minimum bending radius.

Classification

EN 50200 records how long the cable keeps its circuit working. Classification using these results is made under EN 13501-3, and Annex D of EN 50200 gives information on it. The table of classes for construction products in the services category lists:

ProductStandardsClasses
Small diameter power or signal cables (< 20 mm, conductors ≤ 2.5 mm²)EN 13501-3, EN 50200PH 15, PH 30, PH 60, PH 90, PH 120
Electrical and fibre-optic cables and accessories, conduits and fire protective systems for cablesEN 13501-3P 15, P 30, P 60, P 90, P 120

The number is the classification period in minutes, as defined in EN 13501-3. The test meets Mandate M/117 for the PH classification. Annex B sets the field of direct application and rules for extended application of test results (EXAP).

Annex E water spray and BS 8434-2

Annex E is informative. It gives a means of applying a water spray to the cable during the test. It is not required for PH classification under Mandate M/117. The standard notes that such a requirement may be a feature of particular product standards.

BS 8434-2:2003+A2:2009 modifies the BS EN 50200 test to use a flame temperature of 930 °C (+40/0 °C) and to apply a water spray. Its scope states that compliance with BS 5839-1:2002, 26.2e) may be demonstrated using this method.

How it relates to other standards

StandardRelationship
BS 8491:2008UK method for large power cables, overall diameter above 20 mm, for smoke and heat control and certain other active fire safety systems
IEC 60331-2IEC flame and shock test (at least 830 °C) for cables up to 20 mm. A separate test with its own apparatus and procedure
EN 13501-6Reaction to fire classes (Aca to Fca). EN 50200 is about resistance to fire, which is a separate property

The 2015 edition removed the detailed procedures for metallic data and optical fibre cables, which moved to the CLC/TC 46X and CLC/TC 86A standards. It also replaced the old Annex D with the new Annex B (field of application and EXAP) and Annex D (classification).

What it means in practice

  • A PH class only applies to cables up to 20 mm diameter. Larger power cables are assessed differently, for example to BS 8491.
  • Where a specification calls for a water spray test, check whether it means BS EN 50200 Annex E or BS 8434-2.
  • The result is valid for the clips used in the test. If alternative clips were agreed for multicore cable, the result only applies when the cable is installed with those clips.
  • A PH class is about resistance to fire only. Check the CPR reaction to fire class separately.

Related reading: What is LSZH cable and when do you need it?.