Testing

ISO/IEC 14763-3: Testing of Optical Fibre Cabling

Inspection and test methods for installed optical fibre cabling: light source and power meter, OTDR, test cords, reference connectors and cleanliness.

ISO/IEC 14763-3 Ed. 3.0 2024 4 min read

Edition
3.0
Published May 2024
Methods
LSPM and OTDR
Single fibre and MPO
Single-mode
Up to 10 km
Range supported in Ed. 3
Full titleInformation technology. Implementation and operation of customer premises cabling. Part 3: Testing of optical fibre cabling
PublisherISO and IEC, joint technical committee ISO/IEC JTC 1/SC 25
Current editionEdition 3.0, 2024-05. Replaces Edition 2 (2014) and Amendment 1 (2018)
StatusCurrent. IEC stability date 2028. An amendment is at working draft stage
Related standardsISO/IEC 11801-1, ISO/IEC 14763-2, IEC 61280-4-1, IEC 61280-4-5, IEC 61300-3-35, IEC 61746-1/-2, IEC 61315

What it covers

ISO/IEC 14763-3 specifies systems and methods for inspecting and testing installed optical fibre cabling. It applies to cabling designed to premises cabling standards, including the ISO/IEC 11801 series, and installed to ISO/IEC 14763-2.

Where a standards-based test procedure already exists, the document refers to it. The quality plan for each installation, prepared under ISO/IEC 14763-2, sets which acceptance tests are run and the sampling level.

Changes in Edition 3

  • Plastic optical fibre testing removed
  • Testing of MPO (multi-fibre) cabling added
  • End-to-end (E2E) link and MPTL testing with a light source and power meter (LSPM) added
  • Measurement uncertainty given for every method
  • Normative visual inspection for cleanliness, aligned with the ISO/IEC 11801 series
  • Single-mode testing to 10 km
  • Reference connectors described, with new attenuation limits for connectors measured against them
  • Recommended cleaning methods added

Structure

Clause or annexSubject
5Test equipment: light source, power meter, OTDR, test cord connectors, test cords, visual inspection equipment
6Testing: reference planes, wavelength, direction, cleanliness, tests of installed cabling
7Performance assessment of installed components using an OTDR
8Test result documentation
Annex A (normative)Test cord attenuation verification
Annex B (informative)Quality planning
Annex C (informative)Example calculations of channel and permanent link limits
Annex D (informative)Optional end-face inspection of test connectors
Annex E (normative)Cleaning of LC, LC/APC and single-mode MPO APC interfaces
Annex F (normative)MPO to MPO link testing, enhanced three-test-cord method

Tests on installed cabling

ClauseTest
6.9.2Attenuation of single fibre connector cabling, by LSPM
6.9.3Attenuation of multi-fibre (MPO) connector cabling, by LSPM
6.9.4Attenuation of links and channels, by OTDR
6.9.5Propagation delay
6.9.6Length
6.9.7 to 6.9.9Fibre continuity, cabling polarity and fibre core size

Reference planes are defined for channels, links, permanent links, E2E links and MPTL. Clause 7 adds OTDR assessment of cable attenuation, test interfaces, connecting hardware, joints, return loss and fibre length. It also covers bi-directional measurement and the parameters that define what an OTDR can measure, including dynamic range, pulse width, averaging time, dead zone, group index and event threshold.

Test cords and reference connectors

Test cords are fitted with reference connectors. These are connectors made to tighter tolerances (Clause 5.6.3 and the IEC 61755 reference-connection standards) so that their own loss is low and repeatable. Clause 5.6 gives mechanical requirements for single fibre and multi-fibre reference connectors, multimode and single-mode, and attenuation test limits for connectors.

  • LSPM cords: launch test cord, tail test cord and substitution test cord.
  • OTDR cords: launch test cord and tail test cord, so the first and last connectors of the cabling under test can be assessed.
  • Verification: Annex A (normative) sets how test cord attenuation is verified. The standard also shows how test cords are labelled and identified.

Multimode launch conditions are set by IEC 62614-1 and measured to IEC 61280-1-4 (encircled flux). Power meters are calibrated to IEC 61315 and OTDRs to IEC 61746-1 and IEC 61746-2.

StandardRelationship
ISO/IEC 11801-1Cabling performance limits. Referenced normatively
ISO/IEC 14763-2Planning, installation and quality planning. Referenced normatively
IEC 61280-4-1Multimode attenuation of installed cabling. Referenced normatively
IEC 61280-4-5Attenuation of MPO cabling with MPO test equipment. Referenced normatively
IEC 61280-4-2Single-mode attenuation and optical return loss of installed cabling. Not among the normative references of Edition 3 (it was a normative reference in Edition 2, 2014)
IEC 61300-3-35Visual inspection of connector end faces. Referenced normatively

What it means in practice

  • Inspect and clean every connector before testing. Cleanliness inspection is normative in Edition 3.
  • Check the test report states the configuration tested (link, permanent link or channel) and the reference method.
  • Check the test cords have been verified and are identified on the report.
  • OTDR results show where loss occurs. LSPM results give the end-to-end attenuation compared with the limit.
  • Specifications that still cite the 2014 edition miss MPO testing and the reference connector limits.