EN 50575: CPR Reaction-to-Fire Classes for Cable

EN 50575, the harmonised standard that brings cable under the CPR: classes Aca to Fca, smoke, droplet and acidity grades, AVCP and DoP.

BS EN 50575 2014+A1:2016 3 min read

Harmonised standard
EN 50575
Under the CPR
Mandatory since
1 Jul 2017
End of the coexistence period
Classes
7
Aca to Fca
Full titleEN 50575:2014+A1:2016, Power, control and communication cables. Cables for general applications in construction works subject to reaction to fire requirements
UK editionBS EN 50575:2014+A1:2016
Legal basisHarmonised standard under the Construction Products Regulation, (EU) 305/2011
Classification standardEN 13501-6
Applies toPower, control and communication cables, copper and fibre, installed permanently in buildings and civil engineering works

What EN 50575 does

EN 50575 is the harmonised European standard that brings cables under the Construction Products Regulation. It sets out how a cable’s reaction to fire is tested and classified, how the manufacturer’s production is checked, and what must appear on the Declaration of Performance and the CE marking. It has applied to power, control and communication cables since 1 July 2017.

It covers reaction to fire only: how much a cable contributes to a fire that starts elsewhere. Fire resistance, which is how long a cable keeps working in a fire, is a separate requirement for cables serving life-safety systems.

Reaction-to-fire classes

ClassFire performanceMain testsAVCP system
AcaNon-combustibleEN ISO 17161+
B1caVery limited contribution to fireEN 50399 (30 kW burner), EN 60332-1-21+
B2caVery limited contribution to fireEN 50399 (20.5 kW burner), EN 60332-1-21+
CcaLimited contribution to fireEN 50399 (20.5 kW burner), EN 60332-1-21+
DcaMedium contribution to fireEN 50399 (20.5 kW burner), EN 60332-1-23
EcaA single cable does not propagate flameEN 60332-1-23
FcaDoes not meet Eca (flame spread H > 425 mm)EN 60332-1-24

EN 50399 burns a bundle of cables on a vertical ladder and measures heat release, flame spread and smoke. EN 60332-1-2 applies a small flame to a single vertical cable.

Additional classifications

GradeScaleTestMeaning
Smokes1, s1a, s1b, s2, s3EN 50399; EN 61034-2 for s1a and s1bs1a: at least 80% light transmittance. s1b: at least 60%
Flaming dropletsd0, d1, d2EN 50399d0: none. d1: none lasting more than 10 seconds
Aciditya1, a2, a3EN 60754-2a1 is the least acidic

The additional grades apply to classes B1ca to Dca. Lower numbers are better, so Cca-s1a,d0,a1 is a better result than Cca-s1b,d2,a2.

Assessment and verification of constancy of performance (AVCP)

  • System 1+ (Aca to Cca): a notified product certification body tests the cable, inspects the factory and its production control, keeps it under continuous surveillance and audit-tests samples.
  • System 3 (Dca and Eca): a notified testing laboratory type-tests the cable; the manufacturer runs its own factory production control.
  • System 4 (Fca): no third-party involvement.

What the installer and specifier should check

  • The class printed on the cable, drum or box label, with the CE (or UKCA) marking.
  • A Declaration of Performance (DoP) stating the class, the standard and, for classes Aca to Eca, the notified body involved.
  • That the class meets the specification or the building’s fire strategy. EN 50575 classifies the cable; the minimum class for an installation is set by national rules, specifications or standards such as BS 6701.