ANSI/TIA-568.2: Balanced Twisted-Pair Cabling and Components

The North American standard for twisted-pair cabling and components. Defines Category 5e, 6, 6A and 8 performance, links and channels.

ANSI/TIA-568.2 568.2-E (2024) 4 min read

Current revision
568.2-E
Published October 2024
Standard channel
100 m
90 m permanent link + cords
Category 8 channel
30 m
24 m link + 6 m cords
Full titleBalanced Twisted-Pair Telecommunications Cabling and Components Standard
PublisherTelecommunications Industry Association (TIA), committee TR-42.7
Current revisionANSI/TIA-568.2-E, published 24 October 2024
StatusCurrent. Revises ANSI/TIA-568.2-D (2018) and absorbs its addenda D-1 and D-2.
Related standardsANSI/TIA-568.0, 568.1, 568.3, ISO/IEC 11801-1, EN 50173-1

What it covers

ANSI/TIA-568.2 sets the transmission requirements for balanced twisted-pair cables, connecting hardware, cords, permanent links and channels. It also sets the field test requirements used to certify installed cabling. It is part of the TIA-568 family, alongside 568.0 (generic customer premises), 568.1 (commercial buildings) and 568.3 (optical fibre).

Revision history

DocumentDateNotes
ANSI/TIA-568-C.2-12016Added Category 8
ANSI/TIA-568.2-D2018Replaced 568-C.2. Brought Category 8 into the main standard. Added MPTL and 28 AWG cords.
ANSI/TIA-568.2-D-1April 2019Balun requirements for Category 8 testing
ANSI/TIA-568.2-D-2August 2020Power delivery over balanced twisted-pair cabling. Added DC resistance unbalance limits for Category 5e, 6 and 6A
ANSI/TIA-568.2-EOctober 2024Current revision. Includes D-1 and D-2, corrects errors and updates terms.

Categories and frequency ranges

TIA categorySpecified up toTypical maximum channelNearest ISO/IEC class
Category 5e100 MHz100 m, 4 connectionsClass D
Category 6250 MHz100 m, 4 connectionsClass E
Category 6A500 MHz100 m, 4 connectionsClass EA
Category 82 000 MHz30 m, 2 connectionsClass I

TIA does not recognise Category 7 or 7A. Category 8 is designed for 25GBASE-T and 40GBASE-T and uses the RJ45-style modular interface. It aligns with the ISO Class I approach built from Category 8.1 components.

TermWhat it includesMaximum length
ChannelThe whole path between two active devices, including patch and equipment cords100 m (Category 5e to 6A)
Permanent linkThe fixed cabling between the outlet and the panel, excluding end cords90 m (Category 5e to 6A)
Category 8 channelPermanent link plus cords, no more than two connections30 m
Category 8 permanent linkFixed cabling only24 m, leaving up to 6 m for cords

Modular plug terminated link (MPTL)

An MPTL is horizontal cable terminated with an RJ45 plug at the device end, plugged directly into the device. It is recognised for devices where an outlet and cord are impractical or unsafe, such as wireless access points and security cameras. It is tested with a permanent link adapter at the panel end and a patch cord adapter at the plug end.

Cords

568.2-D added recognition of 28 AWG patch cords in a normative annex, with guidance on DC resistance and insertion loss. Before that, only 24 AWG to 26 AWG cord conductors were recognised. Thinner cords have higher loss, which reduces the permitted channel length.

Temperature and power delivery

Insertion loss rises with temperature. TIA cabling design reduces the maximum horizontal cable length when cabling operates above 20 °C, and unscreened cable needs a larger reduction than screened cable.

568.2-E includes the power delivery content from addendum D-2 as Annex H. For non-engineered channels carrying power it gives:

  • Category 6A or higher cabling recommended
  • maximum ambient temperature of 45 °C
  • minimum cable temperature rating of 60 °C
  • connecting hardware that meets IEC 60512-99-002 for un-mating under load
  • 26 AWG or smaller cords not to be installed in conduit or similar pathways
  • cables left unbundled where possible, or split into smaller bundles

Addendum D-2 extended DC resistance unbalance limits, previously applied only to Category 8, to Category 5e, 6 and 6A. 568.2-E carries them into the main standard. Cabling certified to 568.2-D may not meet these -E limits.

How it relates to other standards

  • ISO/IEC 11801-1 and EN 50173-1 are the international and European equivalents. They use classes for channels and categories for components. TIA uses categories for both.
  • TIA Category 5e corresponds to ISO/EN Category 5 components and Class D.
  • Power delivery over bundled cabling is also covered by ISO/IEC TS 29125 and by the IEEE 802.3 PoE standards.

What it means in practice

  • Check that a test report names the correct revision and limit, for example ‘TIA Cat 6A Perm. Link’ or ‘TIA Cat 6A MPTL’.
  • When re-certifying older work, note that a pass against 568.2-D may not be a pass against 568.2-E because of the DC resistance unbalance limits.
  • Plan Category 8 only for short links, typically in data centres: 30 m channel, 24 m permanent link.
  • For PoE-heavy installs, follow the Annex H guidance on temperature rating, bundling and cord gauge.