+44 (0) 208 191 0156 Mon–Fri 9.30am–16:30pm
Alliance Member
B2B  ·  Manufacturer Direct Pricing Partner Application
0
0
Cabling Standards

ANSI/TIA-568.3: Optical Fibre Cabling and Components

The North American standard for premises optical fibre cabling. Sets cable attenuation, connector and splice loss, polarity and test rules.

ANSI/TIA-568.3 568.3-E (2022) 3 min read

Current revision
568.3-E
Published September 2022
Mated connector pair
0.75 dB
Maximum loss allowance
Splice
0.3 dB
Maximum loss allowance
Full titleOptical Fiber Cabling and Components Standard
PublisherTelecommunications Industry Association (TIA), committee TR-42.11
Current revisionANSI/TIA-568.3-E, published 29 September 2022
StatusCurrent. Addendum 568.3-E-1 is in ballot, with a full revision (568.3-F) planned.
ReplacesANSI/TIA-568.3-D (2016) and its addendum 568.3-D-1 (2019)
Related standardsANSI/TIA-598, ANSI/TIA-568.0, 568.1, 568.2, ISO/IEC 11801-1, EN 50173-1

What it covers

ANSI/TIA-568.3 applies to premises optical fibre cabling and components. It sets requirements for cable, connectors, connecting hardware, patch cords, array cables and transitions, and for the transmission performance and testing of installed cabling.

The main clauses are:

  • optical fibre cable
  • connecting hardware (connectors, adapters and splices)
  • cords, array cables and transitions
  • optical fibre transmission performance and test requirements
  • annexes on connector performance, grandfathered fibre types, maintaining polarity (Annex C), optical branching components, and field-testing guidelines for length, loss and polarity (Annex E)

Revision history

DocumentDateNotes
ANSI/TIA-568.3-DOctober 2016Revision of the optical fibre standard
ANSI/TIA-568.3-D-1January 2019Added OM5 and OS1a names, lime colour for OM5 connecting hardware, and testing of MPO-terminated cabling
ANSI/TIA-568.3-ESeptember 2022Current revision. Includes D-1. Adds connectivity Methods U1 and U2, adds IEC and ISO/IEC fibre designations, removes OM1 and OM2 colour designations, and changes the multimode reference-grade to standard-grade allowance to 0.5 dB.
ANSI/TIA-568.3-E-1In ballotAddendum. Includes extra array polarity variants requested for IEEE 802.3dj.

Recognised fibre types

568.3-E uses the ISO/IEC names OM3, OM4, OM5, OS1a and OS2, alongside the IEC and TIA fibre specification names. Colour designations for OM1 and OM2 were removed in 568.3-E.

Maximum cable attenuation

Cable typeWavelengthMaximum attenuation
Multimode 50/125 µm (OM3, OM4, OM5)850 nm3.0 dB/km
Multimode 50/125 µm (OM3, OM4, OM5)1 300 nm1.5 dB/km
Single-mode, inside plant (OS1a, OS2)1 310 nm and 1 550 nm1.0 dB/km
Single-mode, outside plant (OS1a, OS2)1 310 nm and 1 550 nm0.5 dB/km

OM5 is wideband multimode fibre. Field testing of OM5 is carried out at 850 nm and 1 300 nm.

Loss budget

The link attenuation allowance is the sum of the allowances for cable, connections and splices:

Link loss allowance (dB) = (cable attenuation in dB/km × length in km) + (number of mated connector pairs × 0.75 dB) + (number of splices × 0.3 dB)

ElementMaximum allowance
Mated connector pair (standard grade)0.75 dB
Splice0.3 dB
CableAttenuation coefficient × length

Worked example: a 150 m OM4 link at 850 nm with two mated pairs and no splices. Cable 3.0 × 0.15 = 0.45 dB. Connectors 2 × 0.75 = 1.50 dB. Allowance 1.95 dB.

The standard also gives tighter values for reference-grade test cords used during testing. Test equipment applies these when the reference-grade method is selected.

Polarity

Annex C sets out how to keep transmit and receive in the right place across a link.

CablingMethods
Duplex connectivityConsecutive-fibre positioning and reverse-pair positioning
Array (MPO) connectivityConnectivity Methods A, B and C
Array cabling carrying multiple duplex signalsMethods U1 and U2

All components in a link, including trunks, cassettes and cords, must follow the same method.

Colour coding

568.3 refers to ANSI/TIA-598, Optical Fiber Cable Color Coding, for fibre and cable colours. 568.3-D-1 introduced lime as the colour for OM5 connecting hardware.

How it relates to other standards

  • ISO/IEC 11801-1 and EN 50173-1 use the same OM and OS category names. Their attenuation figures can differ from TIA figures, so check which standard the contract names.
  • ANSI/TIA-568.0 and 568.1 set the cabling topology that 568.3 components are used in.
  • Application standards such as IEEE 802.3 set their own channel loss and length limits, which can be tighter than the cabling allowance.

What it means in practice

  • Calculate a loss budget for every link before testing. A tester needs the length, number of connections and splices to set a pass limit.
  • Test multimode at 850 nm and 1 300 nm, and single-mode at 1 310 nm and 1 550 nm.
  • Check that a test report names TIA-568.3 and the reference method used.
  • Confirm the polarity method on drawings and order trunks, cassettes and cords to that method.
  • Check the application loss limit as well as the cabling allowance. A link can pass 568.3 and still exceed the budget for a high-speed application.

Related reading: Fibre optic loss budget: how to calculate insertion loss · Single-mode vs multimode fibre: OM3, OM4 and OS2 explained.